Hatraco was awarded the contract for 3x Hydraulic start systems which are going to be used as the secondary startsystem for a fire water pump application. As per NFPA-20 requirements for a secondary start system, the start system provides the minimum of 6 times of 15 seconds of start duration.
The Clarke (JD) driven Fire water pumps are going to be deployed at a Techint project in South America. Sensed by a pressure transmitter and a control panel for standalone operation, the start system is automatically recharged by means of an electric motor recharge pump. All of Hatraco's hydraulic start systems are equipped with a manual operated hydraulic pump as well. This enables our clients even to re-charge the system in a black out situation.

 
TECHNICAL INFORMATION
| Project | : | Techint-Petrobras | 
| End user | : | Petrobras | 
| Location | : | South America | 
| EPCC | : | Techint group | 
| Start capacity | : | 6 x 38 Litres | 
| Start requirements | : | 6 times, 15 seconds each | 
| Recharge time | : | within 30 minutes | 
| Engine | : | JD 4045 | 
| Required engine firing speed | : | 110 - 120 RPM | 
| Application | : | JD 4045 (Clarke) diesel engine driven fire water pump | 
| Design code / Certification | : | Accumulator design according to ASME VIII Div 1, U stamped | 
| Specialties | : | Control panel for stand alone operation | 
| 2 start valve manifolds for individual accumulator depletion | 