Hatraco was awarded the propject to design, built and deliver a hydraulic start system as a secondary start system for a Fire Water Pump deployed at Petronas Chemicals MTBE. This start system, with a capacity of 6 x 38 liter accumulators offers sufficient capacity to meet the minimum start duration requirement of 6 x 15 seconds as per NFPA-20 to start a Cat® 18 diesel engine driven fire water pump in case the eletcric startsystems fails to do so.
Sensed by a pressure switch and a control panel for stand a lone operation, the start system is automatically recharged by means of a electric motor recharge pump. All of Hatraco's hydraulic startsystems are equipped with a manual operated hydraulic pump as well. This enables our clients even to re-charge the system in a black out situation.

TECHNICAL INFORMATION
| Project | : | Petronas Chemicals MTBE Sdn Bhd | 
| End user | : | Petronas | 
| Location | : | Malaysia | 
| EPCC | : | Snerycorp | 
| Start capacity | : | 6 x 38 Liter | 
| Start requirements | : | 6 times 15 seconds each | 
| Recharge time | : | within 30 minutes | 
| Engine | : | Caterpillar C18 (Clarke) | 
| Required engine firing speed | : | 110 - 120 RPM | 
| Application | : | Cat C18 (Clarke) diesel engine driven fire water pump | 
| Design code / Certification | : | Accumulator design according to ASME VIII Div 1, U stamped | 
| Specialties | : | 2 start valve manifolds for individual accumulator depletion | 
| Control panel for stand alone operation | 
 